Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module/ Instructions User Manual

Page 20

Advertising
background image

20 SLC 500™ RTD/Resistance Input Module

Publication 1746-IN007C-EN-P - December 2002

The module accuracy is dependent on the RTD/Resistance type, the excitation
current, and the input filter selection. The following table shows the module
accuracy and temperature drift when the module has been auto-calibrated at the
operating temperature and when the module’s temperature changes but has not
been recalibrated.

Input Type

Resistance Range
(0.25 mA
Excitation)

Resistance Range
(1.0 mA Excitation)

Resolution

Repeatability
(28 Hz, 50/60 Hz)

Resistance

150

0 to 150

0 to 150

0.01

±0.04

500

0 to 500

0 to 500

0.1

±0.2

1000

0 to 1000

0 to 1000

0.1

±0.2

3000

0 to 3000

0 to 1200

0.1

±0.2

Advertising