20 SLC 500™ RTD/Resistance Input Module
Publication 1746-IN007C-EN-P - December 2002
The module accuracy is dependent on the RTD/Resistance type, the excitation
current, and the input filter selection. The following table shows the module
accuracy and temperature drift when the module has been auto-calibrated at the
operating temperature and when the module’s temperature changes but has not
been recalibrated.
Input Type
Resistance Range
(0.25 mA
Excitation)
Resistance Range
(1.0 mA Excitation)
Resolution
Repeatability
(28 Hz, 50/60 Hz)
Resistance
150
Ω
0 to 150
Ω
0 to 150
Ω
0.01
Ω
±0.04
Ω
500
Ω
0 to 500
Ω
0 to 500
Ω
0.1
Ω
±0.2
Ω
1000
Ω
0 to 1000
Ω
0 to 1000
Ω
0.1
Ω
±0.2
Ω
3000
Ω
0 to 3000
Ω
0 to 1200
Ω
0.1
Ω
±0.2
Ω