Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module/ Instructions User Manual

Page 18

Advertising
background image

18 SLC 500™ RTD/Resistance Input Module

Publication 1746-IN007C-EN-P - December 2002

Input Specifications

RTD Types

platinum, nickel, nickel iron, copper
(For additional information on RTD types, see page 21.)

Temperature
Scale (Selectable)

°C or °F and 0.1°C or 0.1°F

Resistance Scale
(Selectable)

1

or 0.1

for all resistance ranges except for 150

Ω;

or 0.1

or 0.01

for 150

potentiometer.

Input Step
Response

Refer to the SLC 500™ RTD/Resistance Input Module User Manual, publication number
1747-UM003A.

Channel Turn-On
Time

Requires up to one module update time plus module calibration time.

Channel Turn-Off
Time

Requires up to one module update time.

Reconfiguration
Time

Requires up to one module update time plus module calibration time.

Channel Scan
Time (with lead
resistance)

28 Hz = 250 ms
50/60 Hz = 147 ms
800 Hz = 18 ms
6400 Hz = 10 ms

Channel Scan
Time (without lead
resistance)

28 Hz = 125 ms
50/60 Hz = 75 ms
800 Hz = 10 ms
6400 Hz = 6 ms

RTD Excitation
Current

RTD setting:
0.25 mA - Recommended for use with higher resistance ranges for both RTDs and direct
resistance inputs (1000

RTDs and 3000

resistance input). Refer to RTD manufacturer for

recommendations.

1.0 mA -Recommended to use for all other RTD and direct resistance inputs, except 1000

RTDs and 3000

resistance input ranges are limited. Refer to RTD manufacturer for

recommendations.

Advertising