Module Status Indicator and Display

The Module Status indicator and Module Status display provide
diagnostic information.

Indicator

OK

Display

Cause

Recommended Action

Off

None

The module is not
communicating due to a
power supply fault or internal
fault.

1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is

firmly seated in the chassis.

4. If the indicator remains off,

replace the module.

Red

Reset
Complete-

Change
Switch
Settings

Module’s network address is
set to 00, an invalid
ControlNet address.

1. Remove power from the

chassis.

2. Remove the module from

the chassis.

3. Set the switches to their

final value. See page 10.

4. Replace the module in the

chassis.

5. Apply power to the chassis.

FAIL

This code is displayed when
the power-up test fails.

Replace the module.

Backplane

Init

(1)

The module is waiting for the
redundant module to complete
power up.

None required.