ControlLogix ControlNet Interface Module 29

Publication

1756-IN607A-EN-P - February 2008

ControlNet Channel Status Indicators

ControlNet Indicator States (A AND B)

AND

A

B

Cause

Action

Off

There is no power.

No action is required, or apply
power.

Steady red

Unit has faulted.

Cycle power or reset unit.

If fault persists, contact a
Rockwell Automation
representative or distributor.

Alternating
red/green

A self-test is being conducted.

No action is required.

Alternating
red/off

Node has been configured
incorrectly.

Check network address and other
ControlNet configuration
parameters.

The ControlNet channel status indicators appear in one of these
states:

Steady - status indicator is on continuously in the defined
state.

Alternating - while viewed together, the two indicators
simultaneously alternate between the two defined states. The
two indicators are always in opposite states, out of phase.

Flashing - when each status indicator is viewed apart from the
other, each status indicator alternates between the two defined
states. If both indicators are flashing, they must flash together,
in phase.