6 POINT I/O

Publication 1734-IN510B-EN-P - August 2000

1734-AC Output Modules

1

(1734-OA2)

1734 DC Input Sink Modules

1

(1734-IB2, -IB4)

Specification

Value

Specification

Value

Module Location

1734-TB, TBS, TB3 or -TB3S wiring base assembly

Pointbus Current

75mA maximum @ 5V dc

Power Dissipation

0.8W maximum @ 28.8V dc

Thermal Dissipation

2.7 BTU/hr maximum @ 28.8V dc

Isolation Voltage

Tested at 1500V rms/V ac dc for 1s

Mass

1.09 oz/30.9 grams

External AC Power Supply
Voltage

120/220V ac, 60Hz nominal

External AC Power Supply
Voltage Range

85-264V ac, 47-63Hz

Dimensions Inches

(Millimeters)

2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)

Field Wiring Terminations

0 - Output 0

1 - Output 1

2 - No Connection

3 - No Connection

4 - L2N Return

5 - L2/N Return

6 - L1

7 - L1

Output Specifications

Outputs per Module

2 non-isolated, sourcing

ON-State Voltage Drop

1.0V maximum @ 0.75A

ON-State Voltage Range

74V ac minimum
120/220V ac nominal
264V ac maximum

Delay Time

2

OFF to ON
ON to OFF

1/2 cycle maximum
1/2 cycle maximum

ON-State Current

10mA minimum per channel
750mA maximum per channel

Indicators (field side
indication, logic driven)

2 yellow status
2 green/red status

OFF-State Leakage

2.7mA max

Output Current Rating

1.5A (2 channels @ 0.75A each)

Surge Current

16A for 100ms, repeatable every 10s

Keyswitch Position

8

1

This module is IEC3 120V/220V ac Output Compliant

1

Off/on delay is time from a valid output “on” signal to output energization. On/off delay is time from a valid output “off” signal to output deenergization.

Specification:

Value:

Specification:

Value:

Module Location

1734-TB or -TBS terminal base unit

Pointbus Current

75mA max @ 5V dc

Inputs/Module

2 (1 group of 2) non-isolated, sinking (1734-IB2)
4 (1 group of 4) non-isolated, sinking (1734-IB4)

Input Filter Time

2

OFF to ON: 0-65ms (1ms default)
ON to OFF: 0-65ms (1ms default)

ON-State Voltage

10V dc min
24V dc nominal
28.8 V dc max

ON-State Current

2mA min
4mA nominal @ 24V dc
5mA max

OFF-State Voltage

5V dc max

OFF-State Current

1.5mA min

Input Impedance

5.3K

Ω

max

Keyswitch Position

1

Indicators

2 yellow input status, logic side (1734-IB2)
4 yellow input status, logic side (1734-IB4)
1 green/red network status, logic side
1 green/red module status, logic side

Power Supply

0 - Input 0

6 - Supply

1 - Input 1

7 - Supply

2 - No Conn. (1734-IB2) - Input 2 1734-IB4)
3 - No Conn. (1734-IB2) - Input 3 (1734-IB4)
4 - Common (1734-IB2) - User Supply (1734-IB4)
5 - Common (1734-IB2) - User Supply (1734-IB4)

Power Dissipation

0.7W max @ 28.8V dc (1734-IB2)
0.9W max @ 28.8V dc (1734-IB4)

Thermal Dissipation

2.4 BTU/hr max @ 28.8V dc (1734-IB2)
3.1 BTU/hr max @ 28.8V dc (1734-IB2)

Field Power

Supply Voltage
Voltage Range

24V dc nominal
10-28.8V dc

Isolation Voltage

1250V rms/V ac

Dimensions (HxWxL)

56mm x 12mm x 75.5mm (2.206in x 0.472in x 2.97in)

Mass

1.09 oz/30.90 grams - (1734-IB2)
1.12 oz/31.75 grams - (1734-IB4)

1

1734-IB2 and -IB4 specifications are IEC 1+ 24V dc input compliant

2

Input OFF to ON, and ON to OFF, filter time is the time from a valid input signal to recognition by the module.