1734-counter modules (1734-ij, -ik) – Rockwell Automation 1734 Point I/O Installation Instructions User Manual

Page 9

Advertising
background image

POINT I/O 9

Publication 1734-IN510B-EN-P - August 2000

1734-Counter Modules (1734-IJ, -IK)

1734-Very High Speed Counter Modules (1734-VHSC24, -VHSC5)

Isolation Voltage

Between any 2 sets
of contacts
Customer load to logic

2550V dc for 1s

2550V dc for 1s

Field Power

Supply Voltage
Voltage Range
Supply Current

None required
240V ac max
2A/channel max

4A/module

Initial Contact Resistance

30m

Ω

Operate/Release Time

10ms max

Switching Frequency

1 operation/3s (0.3Hz at rated load) max

Bounce Time

1.2ms (mean)

Min. Contact Load

100

μ

A at 100mV dc

Mass

1.30 oz/36.86 grams

Expected Life of Electrical
Contacts

Min 100,000 operations @ rated loads

Indicators

2 green/red module/network status
2 yellow output status

Power Dissipation

0.5W max @ 28.8V dc

Thermal Dissipation

1.7 BTU/hr max @ 28.8V dc

Dimensions (HxWxL)

56mm x 12mm x 75.5mm (2.206in x 0.472in x 2.97in)

1

Module outputs are not fused. If external fusing is desired, you must provide external fusing.

Specification:

Value:

Specification:

Value:

Specification

Value

Specification

Value

Number of Inputs

1 - 1 group of A/Areturn, B/Breturn and Z/Zreturn

Input Voltage

5V (1734-IJ)
15-24V dc (1734-IK)

Input Current

19.1mA @ 5V dc (1734-IJ); 6.1mA @ 15V dc (1734-IK)
25.7mA @ 6V dc (1734-IJ);10.2mA @ 24V dc (1734-IK)

Maximum ON-State
Voltage

+ 6V (1734-IJ)
For 1734-IK, see pub. 1734-TD002A-EN-P

Input OFF-State Current

<0.250mA max

Input ON-State Current

>5mA

Input OFF-State Voltage

<1.25V dc (1734-IJ) / <1.8V dc (1734-IK)

Input ON-State Voltage

>2.6V dc (1734-IJ); >12.5V dc (1734-IK)

Input Filter Selections (per
A/B/Z group)

Off
10

μ

s

100

μ

s

1.0ms
10.0ms

Maximum Input Frequency 1.0MHz counter and encoder X1 configurations

500kHz encoder X2 configuration (no filter)
250kHz encoder X4 configuration (no filter)

Module Location

1734-TB, -TBS, -TB3, -TB3S wiring base assembly

Pointbus Current

160mA maximum

Keyswitch Position

2

Mass

1.15 oz/32.60 grams

Thermal Dissipation

3.75 BTU/hr maximum @ rated load (1734-IJ)
5.1 BTU/hr maximum @ rated load (1734-IK)

Power Dissipation

1.1W maximum @ rated load (1734-IJ)
1.5W maximum @ rated load (1734-IK)

Isolation Voltage
(minimum)

Prequalified at 1250V ac/rms between:
System side
Chassis ground
A/B/Z inputs

Field Wiring Terminations

0 - A

1 - Aret

2 - B

3 - Bret

4 - Z

5 - Zret

6 - Chassis ground

7 - Chassis ground

External dc Power

No additional external power required to power
module.

DimensionsInches

(Millimeters)

2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)

Specification

Value

Specification

Value

Module Location

1734-TB, -TBS, -TB3, -TB3S wiring base assembly

Keyswitch Position

2

Pointbus Current

180mA maximum

Field Power Bus

24V dc nominal; range 10-28.8V dc

Power Dissipation

1.9W maximum @ rated load (1734-VHSC24)
1.5W maximum @ rated load (1734-VHSC5)

Thermal Dissipation

6.5 BTU/hr maximum @ rated load (1734-VHSC24)
5.1 BTU/hr maximum @ rated load (1734-VHSC5)

Isolation Voltage
(minimum)

Prequalified for 1250V ac/rms between:
Module 1
System side (PointBus)
Chassis ground
A/B/Z inputs
O0/O1 and user power supply
Module 2
System side
Chassis ground
Vaux +
User power supply common

Field Wiring Terminations

Module 1
0 - A

1 - Aret

2 - B

3 - Bret

4 - Z

5 - Zret

6 - Output 0

7 - Output 1

Module 2
0 - Chassis ground

1 - Chassis ground

2 - Return 0

3 - Return 1

4 - -V

5 - -V

6 - +V

7 - +V

External dc Power (does
not represent power
required to supply outputs)

No additional external power required to
power module

Dimensions Inches

(Millimeters)

2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)

Advertising