Troubleshoot the module – Rockwell Automation 1734-OV2E_4E_8E POINT I/O Protected Sink Output Module Installation Instructions User Manual

Page 21

Advertising
background image

POINT I/O Protected Sink Output Module 21

Publication

1734-IN585C-EN-E - December 2005

Troubleshoot the Module

Indication

Probable Cause

Recommended Action

Module Status

Off

No power applied to device.

Apply power applied to device.

Solid Green

Device is operating normally.

Device is operating normally.

Flashing Green

Device needs commissioning
due to configuration missing,
incomplete, or incorrect.

Configure device properly.

Flashing Red

Recoverable fault is present.

1. Cycle power.
2. Configure device properly if
needed.
3. If condition persists, replace
device.

Solid Red

Unrecoverable fault may
require device replacement.

Replace device.

Flashing Red/Green

Device is in self-test.

None

Module Status

Network Status

Status of Output 0

Status of Output 1

Status of Output 2