Set the network address, Network address thumbwheel – Rockwell Automation 1734-AENTR, Series B 1734 POINT I/O Dual Port EtherNet/IP Adapter Installation Instructions User Manual

Page 11

Advertising
background image

1734 POINT I/O Dual Port EtherNet/IP Adapter 11

Publication 1734-IN041B-EN-P - October 2013

Set the Network Address

The thumbwheel switches are set to 999 and DHCP enabled, by default. You can set the
network Internet Protocol (IP) address in the following ways:

Use the thumbwheel switches on the adapter.

Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.

Retrieve the IP address from nonvolatile memory.

The adapter reads the thumbwheel switches first to determine if the switches are set to a
valid number. You set the node address by using the 3-position thumbwheel switch. Press
the + or - buttons to change the number. Valid settings range from

001…254.

When you use the thumbwheel to assign an address and set it to

001, the adapter gateway

address is set to

0.0.0.0. and the subnet mask is 255.255.255.0 . When you use the

thumbwheel to assign an address and set it between

002...254, the adapter gateway address

is set to

192.168.1.1.

The adapter does not have a host name assigned, or use any Domain Name System when
using the thumbwheel settings.

Network Address Thumbwheel

Refer to publication POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP
Adapter User Manual,

1734-UM017

for more information.

0 2

0

1734-AENTR Series B

Module
Status

Network
Activity

Network
Status

Point Bus
Status

System
Power

Field
Power

POINT I O

Link 1
Activity/
Status

IP ADDRESS

44848

Press either the + or - buttons to
change the number and assign the
adapter IP address

Advertising