European hazardous location approval – Rockwell Automation 1734-AENTR, Series B 1734 POINT I/O Dual Port EtherNet/IP Adapter Installation Instructions User Manual

Page 6

Advertising
background image

6 1734 POINT I/O Dual Port EtherNet/IP Adapter

Publication 1734-IN041B-EN-P - October 2013

European Hazardous Location Approval

The following applies when the product bears the Ex Marking

This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential
Health and Safety Requirements relating to the design and construction of Category 3
equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II
to this Directive.

Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.

ATTENTION: This equipment is not resistant to sunlight or other sources of
UV radiation.

WARNING: This equipment shall be mounted in an ATEX certified enclosure
with a minimum ingress protection rating of at least IP54 (as defined in
IEC60529) and used in an environment of not more than Pollution Degree 2
(as defined in IEC 60664-1) when applied in Zone 2 environments. The
enclosure must utilize a tool removable cover or door.

WARNING: Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 140% of the rated voltage
when applied in Zone 2 environments.

WARNING: Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other means provided
with this product.

WARNING: Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous.

WARNING: Enclosure must be marked with the following: "Warning - Do
not open when energized." After installation of equipment into the enclosure,
access to termination compartments shall be dimensioned so that
conductors can be readily connected.

WARNING: Earthing is accomplished through mounting of modules on rail.