Interpret status indicators – Rockwell Automation 1734-AENTR, Series B 1734 POINT I/O Dual Port EtherNet/IP Adapter Installation Instructions User Manual

Page 16

Advertising
background image

16 1734 POINT I/O Dual Port EtherNet/IP Adapter

Publication 1734-IN041B-EN-P - October 2013

Interpret Status Indicators

Refer to the following diagram and table for information on how to interpret the
status indicators.

POINT I/O Dual Port EtherNet/IP Adapter, Series B

Indicator Status for Modules

Indicator Status

Description

Module
status

Off

No power applied to device

Flashing green

Device needs commissioning due to missing, incomplete, or
incorrect configuration.

Solid green

Device operating normally

Flashing red

Recoverable fault.

Complete firmware update, verify address switches.

Solid red

Unrecoverable fault, may require device replacement

Flashing

red/green

Module self-test

43264

0 2

0

1734-AENTR Series B

Module
Status

Network
Activity

Network
Status

Point Bus
Status

System
Power

Field
Power

POINT I O

Link 1
Activity/
Status

Link 2
Activity/
Status

IP ADDRESS

Network status
POINTBus status
System power
Field power

NC

Chas Gnd

C

V

Module status
Network activity

Network address
thumbwheels

Ethernet
RJ-45
connectors

Advertising