Before You Begin

To effectively use your adapter, note the following considerations.

Understand Messaging

Class 3 (Explicit Message) requests through the 1734-ACNR adapter to
a specific POINT I/O module may not always receive a response
from the I/O module. In the case where the I/O module does not
reply to the request, the adapter responds with an error code
indicating a time-out.

Establish I/O Connections

When you power up a POINT I/O system and establish I/O
connections, the outputs transition to the Idle state, applying Idle
state data before going to RUN mode. This occurs even when the
controller making the connection is already in RUN mode.

Configure Autobaud

The adapter cannot reconfigure an I/O module that you previously
configured to operate at a fixed baud rate. When you reuse a POINT
I/O module from another POINT I/O system, configure the module
to autobaud before using it with the 1734-ACNR adapter.

For More Information

The following related publications are available online at URL
http://literature.rockwellautomation.com.

Publication

Publication Number

POINT I/O ControlNet Adapter User Manual

1734-UM008

POINT I/O ControlNet Adapter Release Notes