Set the node address, 8publication – Rockwell Automation 1734-ACNR Point I/O ControlNet Adapter Installation Instructions User Manual

Page 8

Advertising
background image

8

Publication

1734-IN582B-EN-P - February 2005

Set the Node Address

Set the node address using the 2-position thumbwheel switch. Valid
settings range from 01 to 99. Press the + or - buttons to change the

number.

Install a Replacement ControlNet Adapter to an Existing System

ATTENTION

You must use Series C Point I/O modules with the
1734-ACNR. Series A and B Point I/O modules will
not work with the 1734-ACNR.

WARNING

When you insert or remove the module while
backplane power is on, an electrical arc can occur.
This could cause an explosion in hazardous
location installations.

Be sure that power is removed or the area is
nonhazardous before proceeding. Repeated
electrical arcing causes excessive wear to contacts
on both the module and its mating connector.
Worn contacts may create electrical resistance that
can affect module operation.

Module
Status

PointBus
Status

ControlNet A
Status

1734-ACNR

ControlNet B
Status

Field
Power

System
Power

0

A

B

2

43248

Network Node
Address
thumbwheel
Press either the +
or - buttons to
change the
number.