Check safety lockout (slow-opening controls only) – Bakers Pride DRG-40 User Manual

Page 36

Advertising
background image

VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS

9

69-1226—2

4. With main burner operating, check the gas control

flow rate using the meter clocking method or check
pressure using a manometer connected to the
outlet pressure tap on the gas control. See Fig. 6.

5. If necessary, adjust the high pressure regulator to

match the appliance rating. See Tables 8 and 9 for
factory-set nominal outlet pressure and adjustment
range.
a. Remove the pressure regulator adjustment cap

(Fig. 6).

Using a screwdriver, turn the inner adjustment screw for
HI pressure clockwise

to increase or

counterclockwise

to decrease the gas pressure

to the burner.

6. After high pressure has been checked, check low

pressure regulation. Two-stage appliance
operating sequences vary. Consult the appliance
manufacturers instructions for the specific
operating sequence and regulator adjustment
procedure for the appliance in which the control is
installed and for instructions on how to prevent the
control from moving to high stage while checking
the low pressure regulator setting.

7. Check the low rate manifold pressure listed on the

appliance nameplate. Gas control low rate outlet
pressure should match this rating.

8. With main burner operating, check the gas control

flow rate as before (using the meter clocking
method or check pressure using a manometer
connected to the outlet pressure tap on the
control).

9. If necessary, adjust the low pressure regulator to

match the appliance rating. See Tables 8 and 9 for
factory-set nominal outlet pressure and adjustment
range.

a. Remove the pressure regulator adjustment cap

(Fig. 6).

Using a screwdriver, turn the inner adjustment screw for
LO pressure clockwise

to increase or

counterclockwise

to decrease the gas pressure

to the burner.

10. Once high and low pressure have been checked

and adjusted, replace pressure regulator
adjustment cap. If the desired outlet pressure or
flow rate cannot be achieved by adjusting the gas
control, check the control inlet pressure using a
manometer at the inlet pressure tap of the control.
If the inlet pressure is in the nominal range (see
Tables 8 and 9), replace the gas control.
Otherwise, take the necessary steps to provide
proper gas pressure to the control.

Check Safety Lockout (Slow-Opening

Controls Only)

1. With the system power off and the thermostat set

to call for heat, manually shut off the gas supply.

2. Energize ignition control and start timing safety

lockout time. When spark ignition terminates, stop
timing.
When using the VR8105H, VR8205H and
VR8305H step-opening control, the specified
ignition control safety lockout time must exceed 8.5
seconds for the system to function properly.

3. After spark cutoff, manually reopen the gas control

knob. No gas should flow to the main burner.

4. Reset the system by adjusting the thermostat

below room temperature, wait 30 seconds, and
then move the thermostat setting up to call for
heat. Normal ignition should occur.

Table 8. Pressure Regulator Specification Pressures (in. wc).

a

Low Fire setting range for VR8305Q 1/2 in. by 1/2 in. and 1/2 in. by 3/4 in. is 1.5 to 3.0 in. wc.

Model Type

Type of

Gas

Nominal Inlet

Pressure Range

Factory Set Nominal Outlet

Pressure

Setting Range

Step

Full Rate

Step

Full Rate

Standard,
Slow

NAT

5.0-7.0

3.5

3.0-5.0

LP

12.0-14.0

10.0

8.0-12.0

Step

NAT

5.0-7.0

0.9

3.5

None

0.7-1.7

LP

12.0-14.0

2.2

10.0

None

1.4-5.5

Two-stage

NAT

5.0-7.0

1.7 Low
3.5 High

0.9-3.0 Low

a

3.0-5.0 High

LP

12.0-14.0

4.9 Low
10.0 High

3.5-5.5 Low
8.0-11.0 High

69-1226-2.fm Page 9 Thursday, November 13, 2003 12:50 PM