background image

Publication 1732D-IN001B-EN-E - May 2004

DeviceNet 1732 ArmorBlock I/O, Series A 13

The following table describes the auxiliary power indicator.

The following table describes individual I/O status indicators.

This product has been tested at an Open DeviceNet Vendor
Association, Inc. (ODVA) authorized independent test laboratory and
found to comply with ODVA Conformance Test. Please contact the
ODVA website (http://www.odva.org) for listing of products tested by
ODVA independent test labs for further details.

Specifications

Following are specifications for the 1732 ArmorBlock I/O modules.

Auxiliary Power

Indication

Status

None

No Auxiliary Power

Solid Green

Auxiliary Power Present

I/O Status Indicators
Function

Point Indicator

Condition

Outputs

None
Yellow

Output not energized
Output energized

Inputs

None
Yellow

No valid input
Valid input

DeviceNet 1732 ArmorBlock I/O Series A

Input Specifications

Inputs

61131-2 Type 3 Compatible

Sensor Source Current, Maximum (per input)

50mA

Sensor Source Current, Maximum (per module)

400mA

Sensor Source Voltage

(auxiliary power=12-30V dc)

Maximum

Minimum


30V

11V

On-state Voltage

Maximum

Minimum


30V dc

11V dc

On-state Current, Maximum

5mA

Off-state Voltage, Maximum

5V dc

Off-state Current, Maximum

1.5mA

Input Delay Time - ON to OFF and OFF to ON, Maximum

0-16000

µs

Output Specifications

Outputs

61131-2 Compatible

Off-state Peak Blocking Voltage, Minimum

30V

On-state Voltage Drop, Maximum

0.5V

On-state Current, Maximum

0.5A

Off-state Leakage, Maximum

50

µA

Module Current, Maximum (all outputs)

4.0A

Surge Current for 10ms, repeatable every 2s, Maximum

1.2A