4 DeviceNet 1732 ArmorBlock I/O, Series A

The rotary switches are read periodically. If the switches have been
changed since the last time they were read and they no longer match
the on line address, a minor fault will occur, which is indicated by a
flashing red MOD LED. Settings between 64 and 99 cause the module
to use the last valid node address stored internally. Example: The last
setting internally was 40. If a change is made to 68, and then you
power up, the address will default to 40.

The module is equipped with AutoBaud detect. AutoBaud lets the
module read the settings already in use on your DeviceNet network
and automatically adjusts to follow those settings.

Set Node Address
This example shows the default
node address set at 63.