Indicator status for modules – Rockwell Automation 1734-AENT, Series B 1734 POINT I/O EtherNet/IP Adapter Installation Instructions User Manual

Page 18

Advertising
background image

18 1734 POINT I/O EtherNet/IP Adapter

Publication 1734-IN042B-EN-P - October 2013

Network
Activity

Off

No link established.

Flashing green/Off

Transmit or receive activity present.

Steady green

Link established.

Network
status

Off

Device not initialized. The module does not have an IP address.

Flashing green

No CIP connections present. Device has an IP address, but no CIP
connections are established.

Green

CIP connections present. Device online and has an IP address, and
CIP connections are established.

Flashing red

One or more CIP connections in timed-out state. Check for I/O
module failure and controller operation.
Note: This does not apply to POINTGuard I/O connection timeout.

Solid red

Duplicate IP address detected.
Verify IP address setting and correct, as needed.

Flashing red/green

The module is performing a self-test (only occurs during cycle

power test).

POINTBus
status

Off

Device not powered – check module status indicator.

Flashing red/green

LED cycle power test present.

Flashing red

Recoverable fault occurred:
• At cycle power the number of expected modules does not equal

the number of modules present

• A module is missing
• Node fault (I/O connection timeout) occurred.

Solid red

Unrecoverable fault occurred – the adapter is bus off.

Flashing green

Firmware (NVS) update in progress.

Solid green

Adapter online with connections established (normal operation,
Run mode).

System
power

Off

Not active; field power is off or DC-DC converter problem present.

Solid green

System power is on; DC-DC converter is active (5V).

Field power

Off

Not active; field power is off.

Solid green

Power is on; 24V is present.