Environmental specifications – Rockwell Automation 1734-AENT, Series B 1734 POINT I/O EtherNet/IP Adapter Installation Instructions User Manual

Page 22

Advertising
background image

22 1734 POINT I/O EtherNet/IP Adapter

Publication 1734-IN042B-EN-P - October 2013

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 30...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:

±4 kV @ 5 kHz on power ports

±3 kV @ 5 kHz on communications ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80% AM from 150kHz...80MHz

Environmental Specifications

Attribute

Value