Environmental specifications, General specifications – Rockwell Automation 1734-AENT, Series B 1734 POINT I/O EtherNet/IP Adapter Installation Instructions User Manual

Page 21

Advertising
background image

1734 POINT I/O EtherNet/IP Adapter 21

Publication 1734-IN042B-EN-P - October 2013

Module input

10...28V DC @ 1000 mA

POINTBus output, max

5V DC @ 1.0A

Dimensions (HxWxD), approx.

76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.)

Enclosure type rating

None (open-style)

Terminal base screw torque

0.8 Nm (7 lb-in)

Weight, approx.

255 g (0.56 lb)

Wiring category

(1)

,

(2)

1 – on power ports

1 – on communications ports

Wire Size

Power connections:
0.34... 2.1 mm

2

(22...14 AWG) solid or stranded copper wire

rated @ 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.) insulation
max or 90

°C (194 °F ) for ControlLogix.

Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category
5e min cable according to TIA 568-B.1 or Category 5 cable
according to ISO/IEC 24702.

North American temp code

T4A

IEC Temp Code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-IN041

.

(2)

Use the Conductor Category information for planning conductor routing as described in the appropriate System Level
Installation Manual.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20...55 °C (-4...131 °F)

Temperature, surrounding air, max

55 °C (131 °F)

Temperature, nonoperating

IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)

IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)

IEC60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):

-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5...95% noncondensing

General Specifications

Attribute

Value