Rockwell Automation 1738-IE4CM12 ArmorPoint 4-Channel 24V dc Analog Input Modules, Series A User Manual

Page 15

Advertising
background image

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 15

Publication

1738-IN024C-EN-P - March 2010

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz

3V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±3 kV at 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line (DM) on signal ports

±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Certifications

Certification (when

product is marked)

(1)

Value

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR11; Industrial Emissions

(1)

See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates,
and other certification details.

Environmental (Continued)

Attribute Value

Advertising