Rockwell Automation Publication 1753-IN001C-EN-P - June 2010

OPC Server

The GuardPLC 1600 controller is an OPC client. An OPC server, catalog number 1753-OPC,
is available from Rockwell Automation and lets computer applications read and write data to and
from the GuardPLC controller.

MAC Address

The media access control (MAC) address of the controller can be found on the label positioned
over both lower RJ45 connections.

Connections for Nonsafety-related Communication

The three 9-pin D-shell connectors on the front of the controller provide the following
communication options.

The pin assignments of the D-shell connector are listed in this table.

IP Address and System ID (SRS)

A transparent label provided with the controller can be used to note the IP address and system
ID (SRS). The default value for the IP address is 192.168.0.99. The default SRS is 60000.

Designation

Function

COMM1 (RS-485)

Modbus Slave (1753-L28BBB-M)
Profibus-DP-Slave (1753-L28BBB-P)

COMM2

Not used

COMM3 (RS-485)

GuardPLC ASCII protocol

Connection

Signal

Function

1

2

RP

5V, decoupled with diodes

3

RxD/TxD-A

Receive/transmit data A

4

CNTR-A

Control signal A

5

DGND

Data reference potential

6

VP

5V, positive pole of supply voltage

7

8

RxD/TxD-B

Receive/transmit data B

9

CNTR-B

Control signal B

IMPORTANT

If you attach the label to the controller, make sure you do not cover any of the
ventilation slots.