Status Indicators

Indicator

State

Description

24V DC

On

24V DC operating voltage present.

Off

No operating voltage.

RUN

On

This is the normal status of the controller.
A routine, which has been loaded into the controller, is executed.
The controller processes input and output signals, carries out communication, and
performs hardware and software tests.

Flashing

The controller is in STOP mode and is not executing a routine.
All system outputs are reset.
STOP mode can be triggered by setting the Emergency stop system variable to TRUE
in the routine, or by direct command from the programming software.

Off

The controller is in ERROR_STOP mode (see ERROR).

ERROR

On

A hardware error has been detected by the controller. The controller goes to
ERROR_STOP mode and the execution of the routine is halted. Hardware errors
are errors in the controller, errors in one or more of the digital input and output
modules, or errors in the counters.

A software error in the operating system has been detected by the controller.

The watchdog has reported an error due to exceeded cycle time.

All system outputs will be reset and the controller ceases all hardware and software
tests. The controller can only be restarted by a command from the programming
software.

Off

No errors are detected.

PROGress

On

The upload of a new controller configuration is in progress.

Flashing

The upload of a new operating system into the nonvolatile ROM is in progress.

Off

No upload of controller configuration or operating system in progress.

FORCE

On

The controller is executing a routine (RUN) and FORCE mode is activated by the user.

Flashing

The controller is in STOP mode, but forcing has been initiated and will be activated
when the controller is started.

Off

Forcing is OFF.

FAULT

On

The routine (logic) has caused an error.

The controller configuration is faulty.

The upload of a new operating system was not successful and the operating
system is corrupted.

Flashing

An error has occurred during a nonvolatile ROM write cycle.

One or more I/O errors have occurred.

Off

None of the above errors has occurred.

OSL

Flashing

Emergency Operating System Loader is active.

BL

Flashing

Boot Loader unable to load operating system or unable to start COMM operating
system loader.

Controller status can be interrogated through the programming software. For more information, see the
GuardPLC Controller Systems User Manual, publication

1753-UM001

.