17

Rockwell Automation Publication 1753-IN001C-EN-P - June 2010

Communication via GuardPLC Ethernet protocol is indicated by two small status indicators
integrated into all connecting sockets.

Additional nonsafety-related communication occurs on the field buses and is indicated by these
status indicators.

Specifications

Indicator

State

Description

Green

On

Full-duplex operation

Flashing

Collision

Off

Half-duplex operation, no collision

Yellow

On

Connection established

Flashing

Interface activity

Indicator

Connection

Description

Green

COMM 1

RS-485 interface, field bus active

COMM 2

Unassigned

COMM 3

Unassigned

Technical Specifications – GuardPLC 1600 Controllers

Attribute

1753-L28BBB-M, 1753-L28BBB-P

User Memory

250 KB max user program memory

250 KB max application data memory

Watchdog, min

10 ms

Safety time, min

20 ms

Current consumption

8 A max (with max load)
0.5 A idle current

Operating voltage

24V DC, -15% to 20%, w

ss

15% (from a power supply with protective

separation conforming to IEC 61131-2 requirements)

Isolation voltage

50V (continuous), Basic Insulation Type, I/O to Ethernet and Ethernet to DC
power

Wiring category

(1)

Category 2 on communication ports, signal ports, and power ports

Wire size

I/O – 0.13…1.3 mm

2

(26…16 AWG) solid or stranded copper wire rated at

75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max

Power – 0.33…2.1 mm

2

(22…14 AWG) solid or stranded copper wire rated

at 75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max

Ethernet – RJ45 connector according to IEC 60603-7, 2-pair or 4-pair

Category 5e minimum cable according to TIA 568-B.1, or Category 5 cable
according to ISO/IEC 24702

Comm: 9-pin D-sub

Wire type

Shielded on Ethernet

Terminal block torque

0.51 N•m (4.5 lb•in)

Advertising