Wire the Expansion Blocks

The following figures show the wiring information for the
expansion blocks.

1790-T16BVOX Input Expansion Block Wiring Diagram

For inputs 0-7: Sinking inputs - wire COM 0 (pin 9) to Field Power (-) GND

Sourcing inputs - wire COM 0 (pin 9) to Field Power (+) 24V dc

For inputs 8-15: Sinking inputs - wire COM 1 (pin 11) to Field Power (-) GND

Sourcing inputs - wire COM 1 (pin 11) to Field Power (+) 24V dc
Note: both COM 0 are internally connected - COM 0 is used for inputs 0-7, COM
1 is used for inputs 8-15. Both COM 1 are internally connected.

1790-T8BV8VX Input/Output Expansion Block Wiring Diagram

Sinking inputs - wire COM (pin 9) to Field Power (-) GND

Sourcing inputs - wire COM (pin 9) to Field Power (+) 24V dc
Note: both COM (pins 9 and 10) are internally connected.

Sinking outputs -wire VDC (pin 11) to Field Power (+) 24Vdc,

wire GND (pin 12) to Field Power (-) GND

20

18

16

14

12

10

8

6

4

2

19

17

15

13

11

9

7

5

3

1

IN15

IN11

COM1

IN7

IN3

IN13

IN9

COM0

IN5

IN1

IN12

IN8

COM0

IN4

IN0

IN14

IN10

COM1

IN6

IN2

20

18

16

14

12

10

8

6

4

2

19

17

15

13

11

9

7

5

3

1

OUT7

OUT3

GND

IN7

IN3

OUT5

OUT1

COM

IN5

IN1

OUT4

OUT0

COM

IN4

IN0

OUT6

OUT2

VDC

IN6

IN2

Advertising