16 POINT I/O 2 Relay Output Module

Publication 1734-IN587B-EN-P - March 2002

Indicator

Indication

Probable Cause

Network Status

Off

Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status
indicator

Flashing Green

Device is on-line but has no connections in
the established state.

Green

Device on-line and has connections in the
established state.

Flashing Red

One or more I/O connections in timed-out
state

Red

Critical link failure - failed communication
device. Device detected error that prevents it
communicating on the network.

Flashing
Red/Green

Communication faulted device - the device
has detected a network access error and is in
communication faulted state. Device has
received and accepted an Identify
Communication Faulted Request - long
protocol message.

Indicator

Indication

Probable Cause

I/O Status

Off

Output is off.

Yellow

Output is on.