18 POINT I/O 2 Relay Output Module

Publication 1734-IN587B-EN-P - March 2002

Specifications

Specifications - 1734-OX2 Output Relay Module

Outputs per Module

2 Form C isolated (normally open; normally closed)
electromechanical relays

Off-State Leakage
Current (max at 240V ac)

2.0mA and bleed resistor thru snubber circuit

Output Voltage Range (load
dependent)

5-28.8V dc @ 2.0A resistive
48V dc @ 0.5A resistive
125V dc @ 0.25A resistive
125V ac @ 2.0A resistive
240V ac @ 2.0A resistive

Output Current Rating
(at rated power)

Resistive
2A @ 5-28.8V dc
0.5A @ 48V dc
0.25A @ 125V dc
2A @ 125V ac
2A @ 240V ac
Inductive
2.0A steady state @ 5-28.8V dc, L/R = 7ms
0.5A steady state @ 48V dc, L/R = 7ms
0.25A steady state @ 125V dc, L/R = 7ms
2.0A steady state, 15A make @ 125V ac,
PF = cos

θ

=

0.4

2

.0A steady state, 15A make @ 240V ac,

PF = cos

θ

= 0.4

Power Rating
(steady state)

250W max. for 125V ac resistive output
480W max. for 240V ac resistive output
60W max. for 28.8V dc resistive output
24W max. for 48V dc resistive output
31W max. for 125V dc resistive output
250VA max. for 125V ac inductive output
480VA max. for 240V ac inductive output
60VA max. for 28.8V dc inductive output
24VA max. for 48V dc inductive output
31VA max. for 125V dc inductive output

Output Signal Delay

OFF to ON

ON to OFF

10ms maximum (time from valid output on signal to relay
energization by module)
10ms maximum (time from valid output off
signal to relay deenergization by module)

Initial Contact Resistance

30m

Switching Frequency

1 operation/3s (0.3Hz at rated load) max

Operate/Release Time

10ms max

Bounce Time

1.2ms (mean)

Minimum Contact Load

5mA per point

Expected Life of
Electrical Contacts

Minimum 1,000,000 cycles resistive
100,000 cycles inductive