POINT I/O 2 Relay Output Module 19

Publication 1734-IN587B-EN-P - March 2002

Fusing

Module outputs are not fused. If fusing is desired, you
must supply external fusing.

Indicators

2 green/red module/network status
2 yellow output status

Keyswitch position

7

General Specifications

Module Location

1734-TB or -TBS wiring base assembly

Pointbus Current

100mA max @ 5V dc

Power Dissipation

0.5W max

Thermal Dissipation

1.7 BTU/hr max

Isolation Voltage

Between any 2 sets
of contacts
Customer load to logic

250V continuous (Tested to 2550V dc for 1s)

250V continuous (Tested to 2550V dc for 1s)

Field Power Bus

Supply Voltage
Voltage Range
Supply Current

None required
240V ac max
2A per channel maximum, 4A per module

Dimensions Inches

(Millimeters)

2.21H x 0.47W x 2.97L
(56H x 12W x 75.5L)

Environmental Conditions

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 55°C (-4 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating
Damp Heat):
5 to 95% noncondensing

Shock

Operating

Non-operating

IEC60068-2-27 (Test Ea, Unpackaged Shock)
30g peak acceleration
50g peak acceleration

Vibration

IEC60068-2-6, (Test Fc, Operating)
Tested 5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz