Rockwell Automation 1734-OE4C Installation Instructions User Manual

Page 19

Advertising
background image

POINT I/O 4 Channel Analog Current Output Module 19

Publication

1734-IN034B-EN-P - November 2010

Weight, approx.

36.9 g (1.3 oz)

North American temp
code

T4A

IEC temp code

T4

(1)

Use this conductor category information for planning conductor routing as described in Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)

Temperature,
surrounding air, max

55 °C (131 °F)

Temperature,
nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Emissions

CISPR 11:
Group 1, Class A

General Specifications

Attribute

Value

Advertising