Rockwell Automation 1734-OE4C Installation Instructions User Manual

Page 20

Advertising
background image

20 POINT I/O 4 Channel Analog Current Output Module

Publication

1734-IN034B-EN-P - November 2010

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on shielded ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Environmental Specifications

Attribute

Value

Advertising