Field bridge, Field-pulse transformer board, Field bridge -18 field-pulse transformer board -18 – Rockwell Automation 1395 Digital DC Drive User Manual

Page 30: Figure 1.13 field-pulse transformer boards

Advertising
background image

Publication 2361-5.01 July 1998

1-18

Product Overview

Field Bridge

The field bridge uses four SCRs to convert the single-phase AC
power into a DC output. For the SCRs to conduct, they must be
forward biased and have a pulse applied to their gates. The SCR gate
is enabled by the field-pulse transformer board.

Field-Pulse Transformer Board

The field-pulse tranformer board provides the necessary gate voltage
and current to trigger the SCRs on. This board uses a resistor/
capacitor arrangement to protect the SCRs from rapid voltage
changes.

Figure 1.13
Field-Pulse Transformer Boards

Option 14FX

Standard

G22

G21

D8

J1

C3

R4

D7

F2

F1

L3

L1

R13

G12

R3

C2

G11

T1

T3

Connection to Power Stage

Interface (SCR Gate Pulses)

Connection to SCRs

in PM2 of Field

Connection to SCRs

in PM1 of Field Bridge

G22

Connection to Power Stage

Interface (SCR Gate Pulses)

Connection to SCRs

in PM2 of Field

Connection to SCRs

in PM1 of Field Bridge

G21

J1

R3

R4

C3

C2

T3

T1

T2

T4

G12

G11

F1

F2

L3

L1

R13

D8

D7

R11

R5