Circuit breaker settings – Rockwell Automation 1395 Digital DC Drive User Manual

Page 73

Advertising
background image

Publication 2361-5.01 July 1998

Drive Specifications

A-5

Circuit Breaker Settings

The 1250A DC drive has a 1200A N-frame circuit breaker with a
1200A plug. The circuit breaker should be set as shown in the
following diagram.

Figure 5
Recommended Circuit Breaker Settings (1250A DC Drive)

The 1650A DC drive has a 1600A R-frame circuit breaker with a
1600A plug. The circuit breaker should be set as shown in the
following diagram.

Figure 6
Recommended Circuit Breaker Settings (1650A DC Drive)

The 3000A DC drive has a 3000A SPB-frame circuit breaker. The
circuit breaker should be set as shown in the following diagram.

Figure 7
Recommended Circuit Breaker Settings (3000A DC Drive)

9vtv‡…vƒÃSHTÃSh‡vtÃQyˆt

5

6

7

8

4

3

2

Short Delay

Pickup • x Ir

Engaged

Remove

In = Ir

Push
to
Trip

Digitrip RMS
Trip Unit

9vtv‡…vƒÃSHTÃSh‡vtÃQyˆt

5

6

7

8

4

3

2

Short Delay

Pickup • x Ir

Engaged

Remove

In = Ir

Push
to
Trip

Digitrip RMS
Trip Unit

Long Delay
Setting (I

R

)

1 x I

n

= I

R

Long Delay
Time

7

Sec
At
6 x I

R

Inst
Setting

2.5 x I

n

Breaker Trips
At 6T
Test Amps

3 I

n

Test

Trip Reset

Unit Status