Sensor Type Select - Write Word 1

RTD Type

Bit

03

02

01

00

Sensor type for channels 0…3

Bit

11

10

09

08

Sensor type for channels 4…7

0

0

0

0

Resistance (default)

0

0

0

1

100

 Pt  = 0.00385 Euro (-200…+870 °C)

0

0

1

0

200

 Pt _ = 0.00385 Euro (-200…+380 °C)

0

0

1

1

100

 Pt  = 0.003916 U.S. (-200…+630 °C)

0

1

0

0

200

 Pt  = 0.003916 U.S. (-200…+377 °C)

0

1

0

1

100

 Nickel  0.00618 U.S(-60…+250 °C)

0

1

1

0

200

Nickel  0.00618 U.S(-60…+200 °C)

0

1

1

1

120

 Nickel  0.00672 U.S(-80…+320 °C)

1

0

0

0

10

 Copper  0.00427 U.S(-200…+260 °C)

1001…1111 not used

Thermocouple Type

Bit

03

02

01

00

Sensor type for channels 0…3

Bit

11

10

09

08

Sensor type for channels 4…7

0

0

0

0

mV (default)

0

0

0

1

B

300…1800 °C (572…3272 °F)

0

0

1

0

E

-270…1000 °C (-454…1832 °F)

0

0

1

1

J

-210…1200 °C (-346…2192 °F)

0

1

0

0

K

-270…1372 °C (-454…2502 °F)

0

1

0

1

TXK/XK(L) -200…800 °C (-328…1472 °F)

0

1

1

0

N

-270…1300 °C (-454…2372 °F)

0

1

1

1

R

-50…1768 °C (-58…3214 °F)

1

0

0

0

S

-50…1768 °C (-58…3214 °F)

1

0

0

1

T

-270…400 °C (-454…752 °F)