Installation in zone 1, Installation in zone 22 – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD Module User Manual

Page 5

Advertising
background image

FLEX Ex Thermocouple/RTD Input Module 5

Publication

1797-5.4 - June 2010

7. Remove cap plug (8) and attach another intrinsically safe terminal base

unit to the right of this terminal base unit if required.

Installation in Zone 1

This module must not be exposed to the environment. Provide a suitable

metal enclosure. This module has a protection factor of IP20.

Installation in Zone 22

When the module is installed in Zone 22, the following cabinets must be used:

IVK-ISRPI-V16LC; IVK-ISRPI-V8HYW; or IVK-ISRPI-V8LC. These

cabinets can be purchased from Pepperl+Fuchs GmbH, Lilienthalstrasse 200 

68307 Mannheim, Germany. Information available at

www.pepperl-fuchs.com.
The IS-RPI cabinets (type IVK2-ISRPI-V8LC, IVK2-ISRPI-V8HYW, or

IVK2-ISPRI-V16LC) ensures the basic protection for the intrinsically safe

apparatus of the FLEX Ex I/O system for use in Zone 22. It corresponds

with category 3D according to RL 94/9 EG and with the type label marked

with the following information:

Pepperl+Fuchs GmbH

68307 Mannheim

IVK2-ISRPI-V8LC (or IVK2-ISRPI-V8HYW or IVK2-ISRPI-V16LC)
EX

II 3 D Ex tD A22 IP54 T70 °C

CE

Serial (manufacturing) number

Model

Electrostatic Charge

Protect the system against electrostatic charge. Post a sign near this module:

WARNING Avoid electrostatic charging.

ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA

ELETROSTÁTICA.

For your convenience, a sign that can be cut out and posted is included in this

installation instruction.

ATTENTION

This module cannot be used in an intrinsically safe

environment after it has been exposed to nonintrinsically

safe signals.

Advertising