Inputs – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD Module User Manual

Page 7

Advertising
background image

FLEX Ex Thermocouple/RTD Input Module 7

Publication

1797-5.4 - June 2010

 EN60079-11:2007, Explosive atmospheres - Part 11 : equipment

protection by intrinsic safety "i"

 EN60079-0:2006, Electrical apparatus for explosive gas atmospheres -

Part 0 : general requirements

 EN 60079-26 : 2004, Electrical apparatus for explosive gas

atmospheres - Part 26 : construction, test and marking of Group II
Category 1 G electrical apparatus

 EN61241-0 : 2006, Electrical apparatus for use in the presence of

combustible dust - Part 0: General requirements

 EN61241-11:2006, Electrical apparatus for use in the presence of

combustible dust – Part 11: Protection by intrinsic safety 'iD'

Inputs

Each input can be operated from a thermocouple (TC) or resistance

temperature detector (RTD). Do not apply any nonintrinsically safe

signals to this module.
When using an intrinsically safe electrical apparatus according to EN50020,

the European directives and regulations must be followed.
The channels in this module are electrically connected to each other and have

a common plus-line.

IMPORTANT

When interconnecting several lines, you must consider the
total accumulated power and check for intrinsic safety.

Thermocouple

Flexbus

Bus

uC

+V

Power
Supply

-V

L

H

-

+

+

mV

-

2W RTD

3W RTD

4W RTD

CJC

+

-

GND

irt8custconxn