XM-944 Process/Temperature Terminal Base 23
Publication
GMSI10-IN024A-EN-P - May 2010
Specifications
The following table lists the technical specifications for the XM-944
Process/Temperature Terminal Base.
Note: Power specification is with module installed.
Product Feature
Specification
Power
Module
Consumption
Heat Production
+21.6 to +26.4V dc
Maximum (XM-360): 300 mA
Typical (XM-360): 170mA
Maximum (XM-361, XM-362): 400mA
Maximum: 7.20 Watts (24.6 BTU/hr)
Typical: 4 Watts (14 BTU/hr)
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Conformal Coating
-20 to +65°C (-4 to +149°F)
-40 to +85°C (-40 to +185°F)
95% non-condensing
All printed circuit boards are conformally coated in
accordance with IPC-A-610C.
Physical
Dimensions
Terminal Screw Torque
3.875 W x 3.75 D x 2.25 H inches
9.48 W x 9.53 D x 5.72 H centimeters
7 pound-inches (0.6 Nm)