Interconnect limit – Rockwell Automation 1440-TB-E XM-944 Process/Temperature Terminal Base User Manual

Page 7

Advertising
background image

XM-944 Process/Temperature Terminal Base 7

Publication

GMSI10-IN024A-EN-P - May 2010

Refer to the specifications for the specific module for power consumption
and other requirements.
See XM Power Supply Solutions application technique, publication
ICM-AP005A-EN-E, for additional details.

Interconnect Limit

Total current draw through the side connector cannot exceed 3A. A separate
power connection is necessary if the total current draw of the interconnecting
modules is greater than 3A.

XM Power Supply Requirements

Protection

Listed Class 2 rated supply, or

Fused* ITE Listed SELV supply, or

Fused* ITE Listed PELV supply

Output Voltage

24Vdc ± 10%

Output Power

100 Watts Maximum (~4A @ 24Vdc)

Static Regulation

± 2%

Dynamic Regulation

± 3%

Ripple

< 100mVpp

Output Noise

Per EN50081-1

Overshoot

< 3% at turn-on, < 2% at turn-off

Hold-up Time

As required (typically 50mS at full rated load

* When a fused supply is used the fuse must be a 5 amp, listed, fast acting fuse such as
provided by Allen-Bradley part number 1440-5AFUSEKIT.

TIP

If the total current draw for a row of modules is greater than 3A, consider
connecting power to a module near the center of the rail, rather than at a
module on either end. Insure that there is less than 3A load in either direction
from the module where power is connected.