48 Configuring the XM-720

Relay Parameters

Use the Alarm, Relay and 4-20 mA Output tab in the Configuration Tool to
configure the behavior of the relays in the XM-720 monitor.

In the provided configuration files, the relays are configured to function as
described in Table 3.4.

Refer to Files to Use With Your XM-720 Monitor on page 39 for a list of the
provided configuration files.

Table 3.4 Pre-Configured Relay Functionality

IMPORTANT

Making a change to the relay parameters may possibly
change the intended function of the relay and front panel
LED.

Configuration Tool
Relay Number

Front Panel
LED

Back Panel
Connection

Intended Function

1

Module Fault

N/A

Indicates a module fault, such as a hardware or
firmware failure.
Turns on the Module Fault LED on the front panel.

2

Xducer Fault

N/A

Indicates transducer DC bias on either channel is
out-of-range.
Turns on the Xducer Fault LED on the front panel.

3

N/A

Fault Relay

Indicates a module fault and/or transducer DC bias is
out-of-range.

4

Warning

Warning
Relay

Indicates that the overall measurement in either
channel exceeds either the alert level thresholds or the
danger level thresholds.
Turns on the Warning LED on the front panel.

5

Trip

Trip Relay

Indicates that the measurement in either channel
exceeds the danger level thresholds.
Turns on the Trip LED on the front panel.