Signal conditioner connections – Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual

Page 58

Advertising
background image

Publication GMSI10-UM001C-EN-E - June 2011

58 Comparing Connections Between the 5802 and the XM-720

Signal Conditioner
Connections

Table B3 defines the different types of signal conditioning connectors for
5802, and the comparable connectors on the XM-720.

Table A.2 Signal Conditioner Connections

5802 Wiring

Signal

XM-720 Wiring

Signal Conditioner Terminal Strips

403/2100

544M

911S/941/9100

910M/960/960M

TB 2

Description

T/S1

5

4

1

2

Signal A

17

Xducer 1 (+)

4

3

3

3

Common A

18

Xducer 1 (-)

-----

7

7

7

Shield A

19

Chassis GND

-----

-----

-----

2

+24 V

23

Xducer +24 V

9

-----

-----

------

-24 V

24

Xducer -24 V

8

8

8

8

4-20mA Chan A +

25

4-20mA 1 (+)

3

3

3

3

4-20mA Chan A return

26

4-20mA 1 (-)

T/S2

6

7

10

9

Signal B

20

Xducer 2 (+)

8

8

8

8

Common B

21

Xducer 2 (-)

-----

4

-----

5

Shield B

22

Chassis GND

-----

------

-----

-----

+24 V

23

Xducer +24 V

-----

------

-----

-----

-24 V

24

Xducer -24 V

3

3

3

3

4-20mA Chan B +

28

4-20mA 2 (+)

8

8

8

8

4-20mA Chan B return

29

4-20mA 2 (-)

Advertising
This manual is related to the following products: