Environment and Enclosure

ATTENTION

This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not
provide adequate protection to radio communication services in such
environments.

This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA or be approved for the application
if non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.

In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines, for additional

installation requirements, publication

1770-4.1

.

NEMA Standards publication 250 and IEC publication 60529, as

applicable, for explanations of the degrees of protection provided by
enclosures.

WARNING

This equipment must be mounted in an ATEX certified enclosure with a
minimum ingress protection rating of at least IP54 (as defined in IEC60529) and
used in an environment of not more than Pollution Degree 2 (as defined in IEC
60664-1) when applied in Zone 2 environments. The enclosure must utilize a
tool removable cover or door.