Install the controlnet adapter, Xm controlnet adapter 9 publication, Ms cha chb bps a b – Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual

Page 9

Advertising
background image

XM ControlNet Adapter 9

Publication

ICM-IN001B-EN-P - March 2013

Install the ControlNet Adapter

To install the adapter on the DIN rail prior to installing the XM terminal base
units, follow these steps.

1. Position the ControlNet adapter module (A) on a 35 x 7.5 mm DIN

rail (B) at a slight angle.

ATTENTION

Do not remove or replace an adapter module while power is applied.
Interruption of the backplane can result in unintentional operation or machine
motion.

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use zinc
plated yellow-chromate steel DIN rail to assure proper grounding. The use of
other DIN rail materials (for example, aluminum or plastic) that can corrode,
oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.

IMPORTANT

The 1440-DYN02-01RJ Standard Dynamic Measurement module is used
with the 1440-ACNR adapter. No other XM catalog number will work with
the 1440-ACNR adapter.

IMPORTANT

The XM bus must be terminated on each end with a 120 ohm, 1%, 1/4 W
resistor. Because the adapter has an internal terminator resistor, the second
resistor must be installed at the opposite end of the bus.

Cont rolNet XM A

dapter

1440-ACNR

XM

®

MS

CHA

CHB

BPS

A

B

Cont r olNet XM Adapter

1440-ACNR

XM

®

MS

CHA

CHB

BPS

C

31769-M

Advertising