Loading, Connecting and Starting the
Guarded Peer-Link

W

INTERPRET

provides commands to Load, Connect and Start

the Guarded Peer-Link Network functions in the Regent.
These commands are performed from the Execution
Controller Window’s Network Menu.

The Load Network and Connect Network commands must be
performed on each Regent participating in the GPL
communications. Finally, the Start Network command must
be used for each Regent configured with a Net Master port to
start the GPL communications functions for each Network leg.
Details of each of the Network commands are described below.

The Network commands should be used after all other normal
initialization and loading functions of the Regent are
completed. These are listed in Table 5.

Table 5. Commands to Perform Before Network Operations.

Initialize RAMcode

Load I/O Configuration

Load Shared Allocation

Start Inputs and Outputs

Load Serial Ports Configuration

Load Programs

Run Programs

Load Comm Protection

Enable Comm Protection

Load Network

The Load Network command loads the GPL configuration to
the Regent. This command must be performed for each
Regent participating in the GPL communications. During the
Load process W

INTERPRET

loads the Regent with the Input

and Output Templates for GPL communications.
Subsequently the Regent allocates the necessary memory for
the Input and Output Buffers required for GPL.