Industrial Control Services

Figure 12. GPL Cycle Time vs. Amount of GPL Data.

To calculate the amount of GPL data (in bytes) use the
following equation:

GPL Data = (QTYBit * 1 byte) + (QTYWord * 2 bytes) + (QTYFP * 4 bytes)
Where:

GPL Data =

Total Quantity of GPL Data configured for the Network

QTYBit

=

Total number of bit type variables (Digital Inputs, Outputs and
Control Relays)

QTYWord = Total number of word type variables (analog inputs, outputs,

shared registers)

QTYFP

=

Total number of shared floating point registers

For example, consider a GPL configuration as shown in Table
7, which lists the amount and types of data each of four
Regents are configured to output to the GPL Network.