SYSTEM CHECKS

System Checks

1. Once the system settings have been adjusted and the V1000 adjusts/reacts to the heat pump outlet

valves opening and closing, the system is ready to operate on its own.

2. Return each heat pump 2-way control valve to its normal operating setting, so it is allowed to open

and close based on the heat pump status.

3. Monitor the system as it reacts to the heat pump 2-way control valves. It is recommended that each

heat pump shall manually meet its set point to allow the 2-way control valve to close, ensuring they
provide a 100% off position, allowing the V1000 to power down.

4. Once all the set up procedures and tests have been performed, the Smart Pump Multizone can now

operate as a self contained system.



STOP FREQUENCY: This parameter needs to be set 1-3 Hz below minimum operating frequency for
the lowest flow rate heat pump.



SYSTEM PRESSURE: This parameter is what allows the smart pump to maintain pressure and allows
efficient operation o the geothermal system.



DRY RUN: This parameter must be set to ensure pump protection in case the canister runs dry.



KEY PAD CONTROL OF ON/OFF BUTTONS: This can be selected in the field.

A. If the B1-02 = 0 the “RUN” and “STOP” buttons are ACTIVE on the drive. This is helpful

during set up.

NOTE: If the drive experiences a power loss in this mode, then the drive will have to be
manually restarted by pressing the “RUN” button.

B. If the B1-02 = 1, then the “RUN” and “STOP” buttons are DISABLED on the drive. This allows

the drive to keep its memory in case of a power loss to the drive and there’ll be no need to
restart the drive manually.

NOTE: Faults can not be reset unless the jumper between S1 and SC is cycled, or
parameter B1-02 is changed to “0”.

FINAL DRIVE PARAMETERS

Description Parameter

Default

Setting

Stop Frequency

B5-15

1-3 Hz Below Minimum Operating Frequency

System Pressure

B5-19

User Input (PSI)

Dry Run

B5-12

"2" Enabled

Key Pad Control of On/Off Buttons:

B1-02

"1" Key Pad Disabled (Allows memory in case of power outage.)