Start up procedure for closed loop system – Bard STAGED CAPACITY PACKAGED HEAT PUMP QW5S1 User Manual

Page 31

Advertising
background image

Manual

2100-532B

Page

31 of 46

START UP PROCEDURE FOR CLOSED
LOOP SYSTEM

1. Be sure main power to the unit is OFF at disconnect.

2. Set thermostat system switch to OFF, fan switch to

AUTO.

3. Move main power disconnect to ON. Except as

required for safety while servicing,

Do not open

the unit disconnect switch.

4. Check system air flow for obstructions.

A. Move thermostat fan switch to ON. Blower runs.

B. Be sure all registers and grilles are open.

C. Move thermostat fan switch to AUTO. Blowing

should stop.

5. Flush, fill and pressurize the closed loop system as

outlined in manual 2100-099.

6. Fully open the manual inlet and outlet valves. Start

the loop pump module circulator(s) and check for
proper operation. If circulator(s) are not operating,
turn off power and diagnose the problem.

7. Check fluid flow using a direct reading flow meter

or a single water pressure gauge, measure the
pressure drop at the pressure/temperature plugs
across the water coil. Compare the measurement
with flow versus pressure drop table to determine
the actual flow rate. If the flow rate is too low,
recheck the selection of the loop pump module

model for sufficient capacity. If the module
selection is correct, there is probably trapped air or a
restriction in the piping circuit.

8. Start the unit in cooling mode by moving the

thermostat switch to cool. Fan should be set for
AUTO.

9. Check the system refrigerant pressures against the

cooling refrigerant pressure table in the installation
manual for rated water flow and entering water
temperatures. If the refrigerant pressures do not
match, check for airflow problem then refrigeration
system problem.

10. Switch the unit to the heating mode by moving the

thermostat switch to heat. Fan should be set for
AUTO.

11. Check the refrigerant system pressures against the

heating refrigerant pressure table in installation
manual. Once again, if they do not match, check for
airflow problems and then refrigeration system
problems.

NOTE: If a charge problem is determined (high or low):

A. Check for possible refrigerant leaks.

B. Recover all remaining refrigerant from unit and

repair leak.

C. Evacuate unit down to 29 inches of vacuum

D. Recharge the unit with refrigerant by weight.

This is the only way to insure a proper charge.

FIGURE 20

WATER TEMPERATURE and PRESSURE PROCEDURE

10

120

110

100

90

80

70

60

50

40

30

20

0

Pete's test plug

Retaining cap, hand tighten only

Test plug cap

Barbed 90° adapter

MIS-2622

with guage adaptor

Dial face pressure guage

Thermometer