Installation instructions – Bally Refrigerated Boxes BC Air, Electric, and Hot Gas Defrost Blast Coolers User Manual

Page 10

Advertising
background image

- 10 -

INSTALLATION INSTRUCTIONS

DRAIN LINE

If unit cooler is mounted flush to ceiling, the staggered
heigh hanger will provide a positive pitch for drainage of
condenser.
If units are suspended below the ceiling, the installer
should provide adequate pitch to the unit by adjusting
the location of the hanger rod nuts.

Note: Check for adequate drainage by pouring water into
the drain pan.

Insulated copper tube should be run from the drain
connection, sloping at least 4” (102mm) per foot. A trap
outside of the room will prevent warm air entering
through the tubing. Connection should be made to
proper drainage facilities that comply with local
regulations.

If room temperatures are below freezing, it is necessary
to heat the drain line to prevent condensate from
freezing in the drain line. Electric heating cable or
electric tape (by others) is used for this purpose. The
drain line heater should be connected for continuous
operation; it is also recommended that the drain line be
insulated. A heat output of 20 watts per lineal foot of 1”
(25mm) drain line in a 0°F (-18 °C) room is usually
satisfactory. 115 volt cable and tape is available from
your local refrigeration wholesaler. Two 115 volts heaters
(by others) of the same wattage may be wired for use on
230 volt system

ELECTRICAL

Wire system in accordance with governing standards
and local codes. See wiring diagrams on P. 4 for unit
cooler wiring diagram.
Page 2 shows operating current, minimum ampacity and
maximum fuse sizing for fan motors.

Note: Electrical wiring is to be sized in accordance with
minimum ampacity rating.

The defrost termination thermostats, fan delay
thermostats and defrost heater safety thermostat are
factory supplied and factory wired to a terminal block.
See figure and component identification diagram on
wiring diagram for electrical compartment arrangement.

A hinged end panel provides quick access to the
electrical compartment.

INSPECTION
C

areful inspection of all parts when received for loss or

damage in transit is very important - Remember, you, the

consignee, must make any claim necessary against the

transportation company. Shipping damage or missing

parts, when discovered at the outset, will prevent later

unnecessary and costly delays.

Ensure that the electrical characteristics are as ordered.

Save all tags and instruction sheets for reference by

installer and owner.

LOCATION

The unit location in the room should be selected to ensure

uniformair distribution throughout the entire space to be

refrigerated. Make sure that the fan does not blow directly

out or pull in through an opened door and that the product

does not obstruct the free circulation of air.

When installing the unit adjacent to a wall, sufficient

clearance must be provided to allow free air movement to

the coil.

Clearance must be provided at each end of the unit to

allow access to refrigerant piping and electrical

compartment.

See dimensional drawings for clearance requirements.

INSTALLATION

Note: These units draw air through the coil and
discharge air from the fan side (see P. 4).
JBC Unit Coolers are supplied with shipping legs to allow

units to be shipped in an upright position. Units are lifted

into place with shipping skid attached to mounting legs.

Slotted hanger brackets take 1/2” (12.7mm) hanger rods.

For fast, convenient mounting, install washer and nuts on

hanger rods prior to lifting units. Rods may be lifted into

slots and are held securely in place by tangs on hangers

After unit coolers are hung in place, remove shipping legs

from units by removing the two 5/16” (8mm) bolts from

each shipping leg.
Note: Shipping legs must be removed to allow hinged
drain pan to open.

Advertising