Specifications, Capacity, Air flow – Bally Refrigerated Boxes BC Air, Electric, and Hot Gas Defrost Blast Coolers User Manual

Page 2: Correction factors, Specifications (60hz), Capacity data (60hz) - 2, Air flow data (60hz)

Advertising
background image

** No allowance made for fan heat - add 3,410 BTUH (1,000 watt) per HP to room load for motor heat.
* E = Electric Defrost • H = 3 Pipe Hot Gas Defrost • R = Reverse Cycle Hot gas Defrost

SPECIFICATIONS (60Hz)

CAPACITY DATA (60Hz)

- 2 -

EVAPORATOR TEMPERATURE CORRECTION FACTORS

AIR FLOW DATA (60Hz)

ELECTRIC AND HOT GAS DEFROST MODELS

AIR DEFROST

Saturated Evaporator

Temperature

20 °F

10 °F

-0 °F

-10 °F

-20 °F

-30 °F

-40 °F

-6.7 °C

-12.2 °C

-17.8 °C

-23.3 °C

-28.9 °C

-34.4 °C

-40 °C

Correction Factor

1.00

.98

.95

.91

.85

.79

.72

Model

Fin

Spacing

FPI

No.

of

Fans

Capacity** at

20°F (-6.7°C)

Capacity**at

-20°F (-28.9°C)

MBH

10°F TD

KW

4.5°C TD

MBH

10°F TD

KW

4.5 °C TD

BC085A

7

2

84.4

24.8

-

-

BC100A

7

2

99.6

29.2

-

-

BC115A

7

2

114.6

33.7

-

-

BC125A

7

2

124.7

36.6

-

-

BC140A

7

3

140.0

41.1

-

-

BC160A

7

3

159.9

46.9

-

-

BC180A

7

3

179.9

52.8

-

-

BC064*

6

2

75.6

22.2

64.2

18.9

BC077*

6

2

90.7

26.6

77.0

22.6

BC089*

6

2

104.8

30.7

89.0

26.1

BC101*

6

2

119.9

35.1

101.0

29.6

BC110*

6

3

129.5

38.0

110.1

32.2

BC126*

6

3

149.3

43.8

126.9

37.2

BC143*

6

3

169.1

49.6

143.7

42.1

BC059*

5

2

69.7

20.4

59.2

17.4

BC072*

5

2

84.7

24.8

71.9

21.1

BC085*

5

2

99.2

29.1

84.3

24.7

BC097*

5

2

114.6

33.6

97.4

28.5

BC103*

5

3

121.4

35.6

103.1

30.2

BC120*

5

3

141.9

41.6

120.6

35.3

BC138*

5

3

162.6

47.6

138.2

40.5

BC053*

4

2

62.8

18.4

53.4

15.7

BC066*

4

2

77.2

22.6

66.0

19.3

BC078*

4

2

91.4

26.8

77.6

22.7

BC091*

4

2

107.2

31.4

91.1

26.7

BC094*

4

3

110.8

32.5

94.2

27.6

BC112*

4

3

131.2

38.5

111.5

32.7

BC129*

4

3

152.3

44.6

129.4

37.9

Model

Fin

Spacing

FPI

CFM

THROW

(Ft.)

CFM

with

Booster

THROW

(Ft.)

BC085A
BC100A
BC115A
BC125A
BC140A
BC160A
BC180A

7

7

7

7

7

7

7

17560

16480

15480

14600

23190

21630

20310

50

47

44

42

44

41

39

17560

16480

15480

14600

23190

21630

20310

91

86

80

77

80

75

71

BC064*
BC077*
BC089*
BC101*
BC110*
BC126*
BC143*

6

6

6

6

6

6

6

17860

16860

15920

15080

23910

22350

21000

51

48

45

43

45

43

40

17860

16860

15920

15080

23910

22350

21000

93

88

83

78

83

77

73

BC059*
BC072*
BC085*
BC097*
BC103*
BC120*
BC138*

5

5

5

5

5

5

5

18180

17260

16400

15580

24540

23100

21780

52

49

47

44

47

44

41

18180

17260

16400

15580

24540

23100

21780

95

89

86

80

86

80

75

BC053*
BC066*
BC078*
BC091*
BC094*
BC112*
BC129*

4

4

4

4

4

4

4

18520

17760

16880

16120

25230

23910

22650

53

51

48

46

48

45

43

18520

17760

16880

16120

25230

23910

22650

97

93

88

84

88

82

78

Advertising