ELECTRICAL DATA - 550 RPM MODELS 60Hz

M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)

ELECTRICAL DATA - 550 (450) RPM MODELS 50Hz

M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)

NO.

OF

FANS

208-230/3/60

460/3/60

575/3/60

TOTAL

FLA

MCA

MOP

TOTAL

FLA

MCA

MOP

TOTAL

FLA

MCA

MOP

1

2.8

3.5

15

1.3

1.6

15

1.1

1.4

15

2

5.6

6.3

15

2.6

2.9

15

2.2

2.5

15

3

8.4

9.1

15

3.9

4.2

15

3.3

3.6

15

4

11.2

11.9

15

5.2

5.5

15

4.4

4.7

15

5

14.0

16

20

6.5

6.8

15

5.5

5.8

15

6

16.8

21

25

7.8

8.1

15

6.6

6.9

15

8

22.4

26

30

10.4

10.7

15

8.8

9.1

15

10

28.0

31

35

13

16

20

11

11.3

15

12

33.6

41

45

15.6

15.9

20

13.2

16

20

NO.

OF

FANS

200-220/3/50

380-400/3/50

TOTAL

FLA

MCA

MOP

TOTAL

FLA

MCA

MOP

1

2.2

2.7

15

1

1.2

15

2

4.4

4.9

15

2

2.2

15

3

6.5

7.1

15

2.9

3.2

15

4

8.7

9.3

15

3.9

4.2

15

5

10.9

11.4

15

4.9

5.1

15

6

13.1

16

20

5.9

6.1

15

8

17.4

21

25

7.8

8.1

15

10

17.4

21

25

7.8

8.1

15

12

26.2

31

35

11.8

12

15

Advertising