WORKSHEETS - SINGLE CIRCUIT

SINGLE CIRCUIT WORKSHEET

(REFER TO P. 24 FOR GUIDELINES, SEE SAMPLE SELECTION ON P. 28)

1. SYSTEM DATA REQUIREMENTS

EVAP TEMP =

o

F

COND TEMP=

o

F

COMPR. CAPACITY=

Btuh / 1000 =

MBH

COND. DESIGN AMBIENT TEMP=

(AT)

o

F

TD=

(Cond. Temp. - Ambient Temp)

COMPRESSOR TYPE=

OPEN

HERMETIC (Refrigerant cooled)

REFRIGERANT= R

REF. FACTOR=

(see P. 2)

ALTITUDE=

AT SEA LEVEL

or

FEET

ALT. FACTOR=
(See P.2)

2. THR (Total Heat of Rejection) CALCULATION

COMPR. CAPACITY (MBH) X HR f

X

ALT f

X

REF f

=THR (MBH)

X

X

X

=

Where HR f =Heat of rejection factor (see Table 2, P. 25)

ALT f = Altitude/elevation factor (Sea level=1, or above factor)
REF f = Refrigerant Correction factor (R22 = 1)
Alternate refrigerant based on factors from P. 2
R12 = 1/.95 = 1.05, R134a = 1/.94 = 1.06,
R502 = 1/.98 = 1.02, R404A/R507/R407A/B = 1/.97 = 1.03
THR = Total Heat of Rejection (MBH, factored in R22) to be rejected by condenser

3. CONDENSER MODEL SELECTION

Refer to the R22 CAPACITY section (P. 2) and select a condenser at the TD (required above) that will closely match
the above calculated THR value. (NOTE: use the R22 capacity Table. The above calculation has already been
adjusted for alternate types).

For the model selected
record the THR PER 1

o

F TD value =

(B) (see P. 2)

4. ACTUAL CONDENSING TEMP CALCULATION

THR (from sec. 2)

/ value (B)

= ATD (actual Temperature Difference)

/

=

To find the Actual Condensing Temp. (ACT) just add the Actual Temperature Difference (ATD)
to the design Ambient Temperature (AT).

ATD

+

AT

=

ACT

+

=

o

F

NOTE: The Actual Condensing Temp. MUST EQUAL or BE LESS THAN the condensing temp recorded in section 1 above.
This ensures the compressor capacity is maintained when operating the condenser at the designed ambient temperature.

For further assistance please contact your local BALLY sales representative.

JOB REF:

COND. MODEL #