INSTALLATION

INSPECTION

A thorough inspection of the equipment, including all com-
ponent parts and accessories, should be made immediately
upon delivery. Any damage caused in transit, or missing
parts, should be reported to the carrier at once. The con-
signee is responsible for making any claim for losses or
damage. Electrical characteristics should also be checked
at this time to ensure that they are correct.

LOCATION

Before handling and placing the unit into position a review of
the most suitable location must be made. This
condenser is designed for outdoor installation.
A number of factors must be taken into consideration

when selecting a location. Most important is the provision
for a supply of ambient air to the condenser, and removal
of heated air from the condenser area.
Higher condensing temperatures, decreased
performance, and the possibility of equipment failure
may result from inadequate air supply.
Other considerations include:
1. Customer requests
2. Loading capacity of the roof or floor.
3. Distance to suitable electrical supply.
4. Accessibility for maintenance.
5. Local building codes.
6. Adjacent buildings relative to noise levels.

UNITS IN PITS

The top of the condenser must be level with, or above the
top of the pit. In addition, a minimum of 8 feet
(2.5 m) is required between the unit and the pit walls.

MULTIPLE UNITS

A minimum of 8 feet (2.5 m) is required between
multiple units placed side by side. If placed end to end,
the minimum distance between units is 4 feet (1.25 m).

LOUVERS/FENCES

Louvers/fences must have a minimum of 80% free area
and 4 feet (1.25 m) minimum clearance between the
unit and louvers/fence. Height of louver/fence
must not exceed top of unit.

WALLS OR OBSTRUCTIONS

All sides of the unit must be a minimum of 4 feet
(1.25 m) away from any wall or obstruction. Overhead
obstructions are not permitted. If enclosed by three
walls, the condenser must be installed as indicated for
units in a pit.

PLACEMENT

Once a suitable location is selected ensure all the remote
mounting parts (legs and hardware) are available. Refer to
Fig.1 (P. 36) and the dimensional data on pages 6 and 7

- 35 -

for the leg mounting locations. On 8, 10 and 12 fan
models a 90” (2.3 m) channel is also included for
maximum support. Single row 4, 5 and 6 fan models use
a 45” (1.15m) channel.

4 ft

(1.25 m)

min.

8 ft

(2.5 m)

min

8 ft

(2.5 m)

min

8 ft

(2.5 m)

min

4 ft

(1.25 m)

min.

4 ft

(1.25 m)

min.