Integrated heating capacities, 542j – Bryant 549B User Manual

Page 147

Advertising
background image

147

PERFORMANCE DATA — 542J (cont)

INTEGRATED HEATING CAPACITIES

LEGEND

NOTES:

1. Integrated heating capacity ratings shown are not adjusted for the effects of

the indoor-fan motor power and heat. A deduction has been made for defrost-
ing the outdoor coils at temperatures below 40 F.

2. Direct interpolation is permissible. Do not extrapolate.
3. When using auxiliary and/or supplementary heating, the maximum allowable

leaving-air temperature is 140 F.

4. For supplementary glycol coil:

542J150 (12

1

/

2

Tons)

CFM

Return

Air

Temp

F (db)

Temp Air Entering Outdoor Coil (F db at 75% RH)

–10

0

10

17

20

30

40

47

50

60

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

3750

55

40.4

7.81

53.0

8.35

65.6

8.89

74.5

9.27

78.5

9.47

91.9

10.10

120.0

11.00

140.0

11.50

147.0

11.80

168.0

12.60

70

37.7

8.19

49.8

8.85

61.9

9.51

70.3

9.97

74.1

10.20

86.8

11.00

114.0

11.90

133.0

12.50

139.0

12.90

161.0

13.90

80

35.4

8.41

47.1

9.15

58.8

9.89

67.0

10.40

70.8

10.70

83.4

11.50

109.0

12.50

128.0

13.20

134.0

13.60

156.0

14.70

4500

55

40.3

7.98

53.9

8.49

67.5

9.00

77.0

9.35

80.9

9.54

93.8

10.10

123.0

10.90

144.0

11.40

149.0

11.60

167.0

12.30

70

36.7

8.38

49.8

9.00

62.9

9.62

72.0

10.00

75.9

10.30

88.6

11.00

116.0

11.80

136.0

12.50

142.0

12.70

163.0

13.60

80

33.2

8.64

46.4

9.32

59.6

10.00

68.7

10.50

72.6

10.70

85.2

11.50

112.0

12.50

131.0

13.10

137.0

13.40

159.0

14.50

5000

55

41.0

8.11

54.7

8.60

68.4

9.09

78.0

9.43

81.9

9.60

95.0

10.20

124.0

10.90

144.0

11.40

149.0

11.60

165.0

12.10

70

44.7

8.45

55.2

9.07

65.7

9.69

73.1

10.10

76.9

10.30

89.7

11.00

118.0

11.90

138.0

12.50

143.0

12.70

163.0

13.50

80

33.6

8.76

47.0

9.43

60.4

10.10

69.8

10.60

73.6

10.80

86.3

11.60

113.0

12.50

132.0

13.10

139.0

13.40

160.0

14.40

5625

55

42.0

8.27

55.7

8.74

69.4

9.21

79.0

9.54

83.0

9.71

96.2

10.30

124.0

10.90

144.0

11.40

148.0

11.50

164.0

12.10

70

42.7

8.66

54.3

9.24

65.9

9.82

74.1

10.20

77.9

10.40

90.9

11.10

120.0

11.90

140.0

12.50

145.0

12.70

163.0

13.40

80

34.5

8.94

48.0

9.57

61.5

10.20

70.9

10.70

74.7

10.90

87.4

11.60

115.0

12.50

134.0

13.10

140.0

13.40

160.0

14.30

6250

55

44.0

8.43

57.3

8.89

70.6

9.35

79.9

9.67

83.9

9.83

97.3

10.40

124.0

11.00

143.0

11.40

147.0

11.50

160.0

12.00

70

45.7

8.79

56.8

9.37

67.9

9.95

75.6

10.40

79.4

10.50

91.9

11.20

120.0

12.00

140.0

12.50

145.0

12.70

161.0

13.30

80

35.2

9.04

48.8

9.72

62.4

10.40

71.9

10.80

75.7

11.00

88.4

11.70

117.0

12.60

136.0

13.20

142.0

13.40

159.0

14.20

542J180 (15 Tons)

CFM

Return

Air

Temp

F (db)

Temp Air Entering Outdoor Coil (F db at 75% RH)

–10

0

10

17

20

30

40

47

50

60

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

Cap.

kW

3750

55

46.4

9.80

60.8

10.60

75.6

11.34

85.8

11.84

91.4

12.10

110.0

12.96

150.2

14.00

178.2

14.72

189.4

15.08

228.0

16.32

70

39.6

10.04

54.4

10.96

69.8

11.86

80.4

12.48

85.8

12.78

103.4

13.82

141.6

15.02

168.4

15.84

179.0

16.26

214.0

17.64

80

35.0

10.20

50.2

11.20

65.8

12.20

76.8

12.90

81.8

13.24

99.2

14.38

136.0

15.70

161.8

16.60

172.0

17.04

206.0

18.52

4500

55

47.8

10.02

62.0

10.78

77.0

11.48

87.6

11.96

93.2

12.20

112.0

12.98

153.2

13.92

182.2

14.58

193.4

14.90

230.0

15.94

70

40.6

10.26

55.8

11.16

71.2

12.00

82.0

12.60

87.4

12.90

105.4

13.86

144.6

14.98

172.0

15.74

182.8

16.12

220.0

17.36

80

36.0

10.44

51.6

11.40

67.4

12.36

78.4

13.04

83.6

13.36

101.0

14.44

138.8

15.68

165.2

16.52

175.8

16.94

212.0

18.30

5000

55

48.6

10.26

63.0

10.98

78.4

11.64

89.2

12.10

94.8

12.32

113.6

13.06

155.2

13.94

184.4

14.56

195.8

14.86

234.0

15.80

70

41.8

10.50

56.8

11.36

72.6

12.18

83.6

12.76

89.0

13.04

107.2

13.96

147.0

15.00

174.8

15.74

185.8

16.08

222.0

17.24

80

37.2

10.66

52.8

11.62

68.6

12.54

79.8

13.20

85.0

13.50

103.0

14.56

141.4

15.72

168.2

16.52

179.0

16.90

216.0

18.18

5625

55

49.2

10.50

63.8

11.18

79.4

11.82

90.2

12.26

96.0

12.46

115.2

13.18

158.0

14.02

187.8

14.60

198.4

14.84

234.0

15.64

70

42.6

10.72

58.0

11.58

73.6

12.38

84.6

12.92

90.2

13.20

108.6

14.08

149.2

15.08

177.6

15.78

188.4

16.10

224.0

17.14

80

38.2

10.88

54.0

11.84

69.8

12.74

81.0

13.38

86.4

13.68

104.4

14.68

143.4

15.80

170.8

16.58

181.6

16.94

218.0

18.14

6250

55

50.0

10.72

64.6

11.40

80.2

12.00

91.0

12.42

97.0

12.64

116.6

13.30

159.8

14.14

190.0

14.70

200.0

14.92

234.0

15.58

70

43.4

10.96

58.8

11.80

74.6

12.58

85.6

13.12

91.2

13.36

110.0

14.22

151.0

15.20

179.6

15.88

190.2

16.16

226.0

17.12

80

39.0

11.12

54.8

12.06

70.8

12.94

82.0

13.56

87.6

13.86

105.6

14.84

145.0

15.92

172.6

16.66

183.6

17.00

220.0

18.16

Cap. — Capacity (1000 Btuh)
Edb

Entering Air Dry-Bulb Temperature (F)

Ldb

Leaving Air Dry-Bulb Temperature (F)

kW

Compressor and Outdoor-Fan Power Input

RH

Relative Humidity

Ldb F = Edb F +

Total heating cap. (Btuh)

1.10 x airflow cfm

Fluid flow Gpm =

fluid capacity (Btuh)

500 x fluid temperature drop (F)

5