PERFORMANCE DATA — 549B, 549C (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leav-

ing indoor coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering indoor coil

3. SHC is based on 80 F edb temperature of air entering indoor coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

549B120 (10 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

3000/0.03

4000/0.04

5000/0.06

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

136.0

124.0

111.4

141.2

129.0

116.6

145.6

132.0

121.2

SHC

64.6

80.8

96.0

71.2

92.4

111.8

78.6

103.2

121.0

kW

7.51

7.35

7.20

7.61

7.45

7.29

7.72

7.53

7.39

85

TC

132.6

119.6

106.6

137.6

124.4

112.0

140.4

127.4

118.0

SHC

63.6

79.2

94.0

70.6

91.4

110.0

77.0

102.6

118.0

kW

8.40

8.23

8.09

8.50

8.33

8.17

8.58

8.40

8.27

95

TC

127.8

114.6

99.4

133.2

119.4

107.2

136.2

121.8

114.2

SHC

62.2

77.6

90.8

69.6

89.8

107.0

76.8

101.2

113.8

kW

9.36

9.18

9.01

9.48

9.30

9.15

9.56

9.36

9.24

105

TC

122.4

108.8

92.0

127.4

113.6

101.4

130.4

116.0

109.6

SHC

60.4

75.4

87.4

68.0

88.0

101.4

75.4

99.4

109.4

kW

10.41

10.26

10.02

10.53

10.35

10.22

10.63

10.43

10.35

115

TC

116.8

101.8

86.6

121.2

106.6

94.8

123.6

109.2

104.6

SHC

58.6

72.8

84.6

66.0

85.4

94.8

73.4

97.0

104.6

kW

11.58

11.37

11.15

11.68

11.51

11.35

11.76

11.60

11.51

125

TC

110.6

95.8

84.6

114.6

98.4

88.8

117.0

100.8

96.4

SHC

56.4

70.6

83.4

64.4

82.4

88.8

71.4

93.8

96.4

kW

12.87

12.62

12.36

12.97

12.73

12.60

13.03

12.83

12.77

549C024 (2 Tons)

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

600/0.11

800/.13

1000/.16

Air Entering Evaporator — Ewb (F)

62

67

72

62

67

72

62

67

72

75

TC

23.7

26

28.5

25.1

27.4

29.8

26.2

28.4

30.4

SHC

19.1

15.9

12.6

22.5

18.2

13.9

24.9

20.4

14.9

kW

1.22

1.23

1.25

1.23

1.24

1.26

1.23

1.25

1.26

85

TC

22.2

25.1

27.5

24

26.4

28.9

25.3

27.3

29.6

SHC

18.5

15.6

12.3

22

18

13.7

24.1

20.1

14.8

kW

1.4

1.42

1.43

1.42

1.43

1.45

1.42

1.43

1.45

95

TC

20

23.9

26.4

22.4

25.2

27.7

24.3

26

28.5

SHC

17.6

15.2

11.9

21.3

17.6

13.4

23.2

19.9

14.7

kW

1.6

1.63

1.64

1.62

1.63

1.65

1.63

1.64

1.66

105

TC

18.1

21.7

25.2

20.6

23.9

26.5

23

24.6

27.2

SHC

16.9

14.4

11.5

19.6

17.2

13.1

21.9

19.5

14.4

kW

1.81

1.85

1.87

1.84

1.86

1.88

1.86

1.87

1.89

115

TC

16.4

19.5

23.7

19.1

21.1

25

21

22.7

25.6

SHC

15.6

13.6

11.1

18.1

16.3

12.6

20

18.9

14

kW

2.05

2.09

2.12

2.08

2.1

2.13

2.1

2.11

2.14

125

TC

14.7

17

21.1

17.3

18.6

23.3

19.1

19.3

23.9

SHC

14

12.8

10.3

16.4

15.5

12.1

18.1

17.8

13.6

kW

2.3

2.34

2.38

2.34

2.35

2.4

2.36

2.36

2.41

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh)
TC

Gross Total Capacity (1000 Btuh)

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82